Most modern turbines are pretty efficient and their exhaust catalyst systems do a pretty good job cleaning the exhaust. Turbines have a long lead time though, so many data centers are using inefficient recip engines.
My mistake, I was referring to those recip engines.
Gas turbines in combination with steam turbines and extensive exhaust cleaning are what I was having in mind, in proper gas power plant scale, combined with heat recovery and feeding heat into the distributing heating network. That way a combined efficiency of 86% is possible (electricity alone: 58%).
Most modern turbines are pretty efficient and their exhaust catalyst systems do a pretty good job cleaning the exhaust. Turbines have a long lead time though, so many data centers are using inefficient recip engines.
Modern CCGTs emit around 0.34–0.40 tonnes CO₂/MWh. This is about half of OCGT and coal, but not nothing.
Practical it means they will install twice the power generation, not cut CO2 emissions.
My mistake, I was referring to those recip engines. Gas turbines in combination with steam turbines and extensive exhaust cleaning are what I was having in mind, in proper gas power plant scale, combined with heat recovery and feeding heat into the distributing heating network. That way a combined efficiency of 86% is possible (electricity alone: 58%).